Underground storage tanks
Underground storage tanks (USTs) are only allowed in the zoning districts specified in Table 6-1, Permitted uses, with the following conditions:
A. Propane tank: Propane tanks are encouraged to be located above ground, but are allowed to be placed underground in any zoning district with the following conditions:
1) Underground propane tanks must be designed for underground use and be installed and maintained according to manufacturer specifications.
2) Underground propane tanks must be designed with cathodic protection or another method to help prevent tank corrosion.
3) The outer surface of the underground propane tank must have a protective coating and be covered with a material that will not be harmful to the shell of the tank.
4) Underground propane tanks must not be larger than 1,100 gallons.
5) Underground propane tanks must be placed at least 12 inches above the high groundwater table.
B. Design standards: All new USTs other than propane tanks that meet the requirements of section 82-1209.a above must receive a special use permit and meet the following design standards:
1) The facility must have an appropriate method of leak detection.
2) Fill-pipes on tanks must have means to collect spills from delivery hoses.
3) The tanks must have overfill protection, such as automatic shutoff devices which activate at 90 percent UST capacity and restrict flow during deliveries.
4) Tanks and/or piping installed must be double-walled with continuous interstitial monitoring.
5) Tanks must be placed at least 12 inches above the high groundwater table.
6) These requirements for USTs are intended to supplement and not to supersede any other applicable requirements of the State of Rhode Island.
(Ord. of 2-3-2025(1), § 1(Exh. A))